Device support

bussard refuses a device it cannot program safely before it writes anything, rather than attempting and rolling back. This page lists which devices each command supports, the checks that protect a management session, and what is not supported yet.

Supported device masks

A device's mask is the code it reports for its system family, such as 07B0 for System B on twisted pair. Write commands refuse an unsupported mask in the pre-flight, before any write. Support differs by command, and bussard audit uses the same table.

Mask Family Medium plan / apply flash reconstruct describe Notes
0010 System 1 TP1 no no no yes classified but unsupported; program it with ETS
0011 System 1 TP1 no no no yes classified but unsupported; program it with ETS
0012 System 1 TP1 no no no yes classified but unsupported; program it with ETS
0013 System 1 TP1 no no no yes classified but unsupported; program it with ETS
0020 System 2 TP1 no no no yes classified but unsupported; program it with ETS
0021 System 2 TP1 no property-only no yes classified but unsupported; program it with ETS
0025 System 2 TP1 no no no yes classified but unsupported; program it with ETS
0300 System 2 TP1 no no no yes classified but unsupported; program it with ETS
0310 System 2 TP1 no no no yes classified but unsupported; program it with ETS
0311 System 2 TP1 no no no yes classified but unsupported; program it with ETS
0700 System 7 TP1 yes yes yes yes memory-mapped tables (default 0x4000 / 0x4201), A_Authorize required; line-mode reconstruct --line records a stub instead of tables
0701 System 7 TP1 yes yes yes yes memory-mapped tables (default 0x4000 / 0x4201), A_Authorize required; line-mode reconstruct --line records a stub instead of tables
0705 System 7 TP1 yes yes yes yes memory-mapped tables (default 0x4000 / 0x4201), A_Authorize required; line-mode reconstruct --line records a stub instead of tables
07B0 System B TP1 yes yes yes yes tables live in device-allocated segments found via PID_TABLE_REFERENCE; full read and write support
27B0 System B RF yes yes yes yes tables live in device-allocated segments found via PID_TABLE_REFERENCE; full read and write support
57B0 System B KNX-IP yes yes yes yes tables live in device-allocated segments found via PID_TABLE_REFERENCE; full read and write support

The flash column reads property-only on mask 0021 (System 2, such as the Jung IPS 300 SREG KNX IP interface): flash runs an application there only when its load procedure holds property compares and writes alone. It loads no object, never factory-resets the interface, and ends with a read-back of every property it wrote. Every other System 1 and System 2 download (BCU1, BCU2: memory allocation and table writes) is refused before anything is written; program those devices with ETS. The shape decides only on 0021: a System B application whose complete load procedure writes properties alone (no master reset, no segment allocation, no table load) is refused on every other mask, naming the shape, rather than run as a property-only device. The assistant shows a property-only plan but does not write it; bussard flash does.

  • flash supports System B (07B0, and the 57B0 / 27B0 KNX-IP and RF variants), System 7 (0705 / 0701 / 0700) and the property-only procedures on 0021. Another family, a mask that differs between application and device, a System B device whose manufacturer is not the application's, or a load procedure with an operation bussard cannot execute refuses the procedure rather than leaving a device half-flashed. A System B device with no links in your project gets empty address and association tables, as ETS writes them, and then reacts to no group telegram.
  • apply, plan and single-device reconstruct support System B (x7B0) and System 7 (0705 / 0701 / 0700). Another mask is refused with a message naming the mask and the supported families; line-mode reconstruct records it as a stub instead.
  • System 7 tables without product data. These three commands run without a .knxprod, so they assume the usual table addresses. A device that keeps its tables elsewhere reads back as an empty table set, never as wrong links, and must be programmed with bussard flash, which takes the addresses from the product data.
  • System 7 apply needs product data. Each table write ends with a record naming the application it belongs to (PEI type, manufacturer, application number and version), taken from the product data. Without it, apply refuses before it connects; plan still runs.
  • System 7 communication flags. A System 7 device ignores every telegram for an object whose communication flag is off, and ETS switches it off on every object without a link. So a new link on such an object only works once its flag is on. With the device's product data, apply switches the flag on for each newly linked object and off for an object that loses its last link, and plan lists each switch. apply --line does the same with each device's pinned product data. Without product data bussard does not know where the group-object table is: plan names each newly linked object whose flag it could not check. A device that refuses the read of its group-object table is handled the same way; its tables are still read.
  • System B communication flags. The same holds on System B: a full flash clears the flag of every object your project does not link. With the device's product data, plan reads the group-object table and compares it with the table a full flash would write, and names each object whose descriptor changes. apply and apply --line write it with the link tables. Without product data plan names each newly linked object whose flag it could not check.
  • System B link change. With product data, every link change unloads the group-object, association and address tables, reloads all three and restarts the device, as ETS does (KNX 03_05_03 ยง3.9.3.5, ETS capture syn-minimal/apply). apply --line restarts each device it writes. apply waits for the device to answer again, then reads it back. When links and parameters change together, the parameter download sends the one restart; no ETS capture of that combination exists yet. A restart that could not be sent stays pending: the next plan offers it.
  • Unfinished table download. A write of the link tables alone (no product data, restore) first checks the group-object table's load state. When a failed download left it unloaded, the write is refused before anything is sent: apply from your project (with product data) or flash reloads it.
  • System 7 restart. Like ETS, apply restarts a System 7 device after writing its tables (a basic restart). It waits for the device to answer again, then reads the tables back, so the read-back also shows that the write survived the restart.
  • System 7 load-state machines. A System 7 device has four load-state machines (address table, association table, application, PEI program). Some products name a fifth in their load procedure; flash sends no record for it, as ETS sends none.
Details

On System B each table lives in a segment the device allocates: apply opens the table object, requests a segment with LdCtrlRelSegment, reads the placement from PID_TABLE_REFERENCE and writes the image there. It never writes the PID_TABLE property array, which real devices refuse. On System 7 the tables are the memory regions at 0x4000 (address table) and 0x4201 (association table), or wherever the product's load procedure puts them. apply follows the order of ETS 6.4.1's table-only downloads: Unload on LSM 1 and 2, then each table loaded to completion in turn, then, when a flag changes, the group-object table inside a StartLoading/LoadCompleted bracket on LSM 3 (no Unload), then a basic restart. It never rewrites the parameters or the application. The address table is written alone and may fill its segment and no more: the product's segment size, else up to the association table the device reports or the product places. With none of these known (no product data, and a device that does not answer PID_TABLE_REFERENCE), the table may be rewritten at its current length but not grown, and plan says so. Every System 7 table read is bounded the same way: a count octet claiming more entries than the region holds (virgin EEPROM reads 0xFF) is refused, and an image that would not fit is refused before anything is written.

The group-object table is not behind the address table: the program declares it in a segment of its own (<ComObjectTable>), on the Ekinex EK-E72 at 0x41D8. apply reads it there. When a flag changes it rewrites the whole table from the image it read, with only those flag octets changed, as ETS does, and reads the table back. It refuses to do so on a device whose application (LSM 3) is not Loaded.

Supported devices

The mask says whether bussard can talk to a device at all. The device-support list says whether bussard has checked what it writes to that product. It names application programs by the application id bussard.lock pins and the device reports, and puts each in one of three categories:

  • proven: bussard wrote a real device with this application and the read-back matched. Kept by hand; every entry cites the issue or the dated owner statement that records the run.
  • likely: the evidence says bussard's download matches ETS, but bussard has not written a real device with this application. A plan for it says "not confirmed on a real device", and so does the assistant over MCP.
  • unsupported or unknown: a known problem (the entry names its issue and, where the issue gives one, its cause), or an application the list does not name.

proven and likely pass the write gate. bussard device --supported prints the whole list (--json too) with the evidence for each entry: live, house-capture (the offline oracle is identical against an ETS download of a house device), sweep (the ETS sweep over the product catalogue) or issue.

How likely is computed

tools/supported-devices/generate.py computes the likely entries from committed files only, and CI fails when the list is stale. The gate looks an application up by its id (manufacturer, number and version), and the sweep can hold several builds of one id, so rule sweep-1 holds for every build. It takes an application into likely when:

  1. the ETS sweep (tools/ets-sweep/evidence/manifest.json) captured at least one build, and found bussard's image identical to ETS's for every captured build;
  2. the load-control records are identical too;
  3. each comparison covers at least 95 % of the octets bussard places;
  4. no build differs; and
  5. every mask a build has belongs to a family with a proven device.

A build the sweep skipped (ETS's catalogue held another build of the order number) counts neither for nor against an entry; the entry records how many builds were not compared (uncompared). An application with builds on two masks lists both and counts in both rows of the table.

The hand-kept entries are checked against the sweep too: a hand entry's mask must be the sweep's mask for its id, and a proven or likely entry with a differing sweep row stops the generator unless the entry says why.

The family key is the mask. The shape of the load procedure would separate families further, but no committed file records it per application yet. A summary of each application's load-control operations, written by tools/ets-sweep/catalog_apps.py next to its order numbers, would let the key include it.

What likely does not rest on yet: the constructs an application uses are not checked against the synthetic products that isolate them, and a defaults sweep reaches the default branches of a product only. Both are open in issue #1097. Firmware behaviour (timing, load states, restarts) is shown by a proven device alone. An application the sweep reports as differing is listed as unsupported with its issue.

The synthetic products (#596) are not on the list: no real device runs them, and the knx-sim loop runs on loopback, where nothing is refused. The table counts them per family.

What is gated

flash, apply (also --line), restore, replace and the download half of commission, and their MCP tools, refuse an unsupported device before anything is written. Reads are never affected: plan, describe, device, backup and reconstruct work on every device, and plan, describe, device, status and audit print the verdict with its category. The KNXnet/IP settings of an IP interface (its [knxnet] table) are not gated: they are standard properties, not built from the application program. A group write, assign and restart are not gated.

The refusal applies on a gateway that is not loopback, the same rule as the real-gateway opt-in. A simulator cannot be damaged, so the knx-sim loop and the product sweep keep running for products that are not on the list yet, which is how a product gets onto it. To write an unsupported device anyway, back it up first and pass --allow-unsupported; over MCP the human has to say yes to it (see Safety). The result and the history record then say support: forced.

Mask 0701 has no proven device yet, so its applications stay unknown however their sweep reads.

Sweep manifest of 2026-11-14, coverage floor 95.0 %.

Family (mask) Proven Likely Identical, no proven device Known problems Synthetic products
0701 0 0 366 27 6
0705 1 276 0 8 8
07B0 3 797 0 21 41
all 4 1072 366 56 55
Manufacturer Proven Likely Known problems
M-0001 0 37 0
M-0002 1 63 0
M-0004 2 71 6
M-0006 0 6 0
M-0007 0 34 0
M-0008 0 53 3
M-0009 0 35 31
M-000C 0 3 0
M-0048 0 82 2
M-0064 0 12 0
M-0071 0 244 4
M-0072 0 1 0
M-0076 0 2 1
M-0077 0 2 0
M-007C 0 8 0
M-0080 0 5 0
M-0083 0 145 1
M-0085 0 22 0
M-0087 0 1 0
M-008B 0 1 0
M-008E 0 12 0
M-009A 0 16 0
M-00A6 0 6 1
M-00B0 0 1 0
M-00B6 0 49 1
M-00C5 0 28 0
M-00C8 0 17 6
M-00C9 0 32 0
M-00E8 0 5 0
M-00EF 0 21 0
M-00FC 0 12 0
M-00FD 0 11 0
M-0112 1 0 0
M-011E 0 16 0
M-011F 0 6 0
M-0151 0 2 0
M-0159 0 1 0
M-0162 0 3 0
M-017D 0 3 0
M-0182 0 1 0
M-0191 0 1 0
M-020D 0 1 0
M-020F 0 1 0

Kept by hand:

Application Id Product Mask Category Evidence
M-0002_A-A0ED-10 0002A0ED10 ABB BE/S16.230.3.2 binary input 07B0 proven live
M-0004_A-20D7-26 000420D726 Jung 230241SR switch actuator 07B0 likely house-capture
M-0004_A-20DE-22 000420DE22 Jung 230021SU switch actuator 07B0 likely house-capture
M-0004_A-20E0-21 000420E021 Jung 360061SR heating actuator v2.1 07B0 likely house-capture
M-0004_A-3030-23 0004303023 Jung 390041SR LED universal dimmer 07B0 likely house-capture
M-0004_A-7066-11 0004706611 Jung 2116REG 0705 likely house-capture
M-0004_A-A011-13 0004A01113 Jung 3361-1MWW presence detector 0705 proven live
M-0004_A-D142-21 0004D14221 Jung 52921ST F50 push-button module 07B0 proven live
M-0009_A-E0EE-10 0009E0EE10 Hager STXF121 (TXF121) 07B0 unsupported issue
M-0009_A-E0F1-10 0009E0F110 Hager STXC51x (TXC513, TXC515) 07B0 unsupported issue
M-0009_A-E0F2-10 0009E0F210 Hager STXD50x (TXD501, TXD503) 07B0 unsupported issue
M-0009_A-E802-13 0009E80213 Hager STYMS646R (TYMS646R) 07B0 unsupported issue
M-0112_A-0003-10 0112000310 Helios KWL KNX connect 07B0 proven live

Source address check

Every command that opens a connection to a device first checks that no device answers at the address bussard itself sends from: the address the gateway assigned to the tunnel, or 0.0.255 on routing. If one answers, the command refuses before touching anything:

refusing to continue: a device on the bus (mask 07B0) already answers at
1.1.255, the individual address this connection would use as its source.

A device tells its management clients apart by source address and nothing else. With a real device at bussard's address, both parties' telegrams land in one session at the target, and a memory write can be applied for the wrong one while both sides see an acknowledgement. That is silent corruption, so bussard checks first, as ETS does.

The check costs one telegram and about 0.6 seconds. The fix is almost always on the gateway: give the tunnel an address no device owns, since many gateways ship with a default that collides on a busy line. --skip-address-check turns it off for a gateway that misbehaves on the probe; nothing else disables it.

It runs once per tunnel. flash, apply and restore hold one tunnel for the pre-flight and the write, so they check once; commission and replace open several and check on each. Group-only commands (read, write, monitor, capture, learn, test) open no device connection and skip it.

The check proves only that no device answers. It cannot see a second passive tool on the same address, such as another bussard on routing or an ETS session on a second tunnel, and it reports free when the reply is not a device descriptor.

Details

The commands that check are scan, assign, adopt, describe, status <ADDRESS>, plan, apply, flash, restart, reconstruct, backup, restore, replace, commission, audit --live, plan --line / apply --line, interface secure, secure diag, and the MCP tools knx_plan_device, knx_apply_device and knx_interface_secure. Only an A_DeviceDescriptor_Response counts as proof. Under --yes, flash also keeps the pre-flight's device connection for the write phase.

The tunnel budget

A KNXnet/IP tunnelling interface has a fixed number of connection slots, often one to five. Each client holds one while connected: Home Assistant's KNX integration permanently, ETS while a project is online, and every running bussard command, including bussard viz and bussard mcp. A second bussard command started while the first runs needs a second slot.

When every slot is taken, bussard reports it as its own condition, not a timeout, and exits with code 4 (illustrative output):

error: 192.0.2.10:3671 has no free tunnelling connection (E_NO_MORE_CONNECTIONS).
A KNXnet/IP interface has a fixed number of tunnel slots, ...

Retrying does not help until a slot is free. Close another client, wait about two minutes for a crashed one's slot to time out, or run a long-lived observer over routing if the interface supports it. bussard init --gateway <ip> and bussard audit --live print N tunnels, M in use. A write never retries into a full interface, so the refusal comes before anything reaches a device.

On a KNXnet/IP Secure interface each slot belongs to a tunnelling user. With --keyring, bussard picks a user whose slot is free and that no other bussard process on this host holds, and moves on when the interface refuses one. With --secure-user you fix the slot, so pick one Home Assistant does not hold.

Managing the IP interface itself

The commands that manage a KNX IP interface (plan and apply of a device file with a [knxnet] table, describe of the interface, interface secure on|off) reach it over a tunnel to its own address. When no tunnel can do that, bussard opens a KNXnet/IP device management connection to the interface instead, as ETS does. It needs no tunnel slot and no tunnel address:

  • --device-management asks for it. This is the way to reach a factory-fresh interface, which still calls itself 15.15.255.
  • Without the flag, plan, apply and describe switch to it when the interface is the gateway and either has no free slot or another device answers at the tunnel's address. interface secure switches when the interface is the gateway and reports no free slot. Each prints a note: line with the reason.

The tunnel stays the default. bussard opens a device management connection only to a gateway that names the target (or 15.15.255) as its own address, because such a connection reaches the interface whatever address is asked for. On a KNXnet/IP Secure interface it signs in as the management user, with the ManagementPassword the keyring or key store holds for the interface. The writes and the read-back are the same as over a tunnel. Only the carrier differs.

Reconnecting is not a write. knx_bus_reconnect drops the MCP server's connection to the interface and opens a new one. Nothing is sent onto the KNX bus, so it needs only the read tier; in --passive mode the server reconnects on its own. A tool that writes while the bus is down is refused with the last connection error, never queued: a waiting frame is dropped after 2 seconds.

Known limitations

  • KNX Data Secure. bussard programs a Data Secure device with its tool key on flash and apply, and reads one back with describe, plan and reconstruct. The handshake and security-object bytes match ETS, full flashes have completed on real secured devices, and secured group telegrams decrypt on a live bus. One part is inferred: the layout of a sender table (the devices a receiver accepts secured telegrams from) with more than one entry, since every download observed so far writes at most one.
  • Securing a device. bussard operates devices ETS has secured. It does not secure a factory-fresh device from its certificate, re-key one or switch Data Secure off; use ETS. A device that answers only under its factory key, because it was reset or never commissioned, is recognised by describe with the factory key from the key store and named as such. bussard writes nothing under the factory key.
  • KNXnet/IP Secure tunnelling. A secure-only interface needs a tunnelling user, from the key store, --keyring, or --secure-user <id> --secure-password-env <VAR>; without one, bussard refuses at once and names the cause. Secure tunnelling runs against real secure-only interfaces. bussard interface secure on|off, which switches an interface's security, matches an ETS capture step for step but has not yet run against a real interface.
  • Secure session keepalive. Some interfaces drop a session idle for 60 seconds, so bussard sends a keepalive every 30 seconds (BUSSARD_SECURE_KEEPALIVE_SECS changes it; bussard test --secure-idle <secs> measures an interface read-only). The session runs over TCP only, as the KNX standard requires.
  • Calculated parameters. Some programs compute parameter values with a small script instead of storing what you set, such as a thermostat's fan settings or a dimmer's dimming curve. bussard runs these scripts (the VBScript and JavaScript that product data uses). Like ETS, it runs a script only once a value the script reads differs from the product's default; at the defaults the computed values keep their defaults (shown by the ETS captures syn-param-calculation defaults and calc-input). A script it cannot run makes plan, apply and flash refuse that device and name the calculation, rather than write a value the script did not compute. So do calculations that keep changing each other's results, and a value in the device file for a parameter a calculation computes differently: remove it, or change the parameters the calculation reads. bussard device, bussard doc, bussard diff, viz and the MCP project tools show a computed parameter with the value the download writes, marked as computed by its calculation. Verified byte for byte against ETS downloads of Ekinex EK-E72 thermostats (VBScript), a Jung LED dimmer (JavaScript) and the synthetic product that changes a calculation's input.
  • Text parameters. A text parameter is written in the code page its program declares. A program that declares none is written in ISO 8859-1, as ETS does; a character whose octet differs between ISO 8859-1, Windows-1252 and ISO 8859-15 (the euro sign, for example) or lies beyond U+00FF is refused there. A declared code page bussard does not know takes ASCII only.
  • System 1 and System 2. BCU1 and BCU2 devices are identified and described, but not programmed, except the property-only applications on 0021 above.
  • Not implemented: secure routing (multicast).

Next steps