The commands that listen to group telegrams, read and write group values, name addresses from live traffic and run acceptance tests: monitor, capture, read, write, learn and test. Global options and exit codes are on Global options.

bussard monitor

Live-monitor the bus and decode each telegram against the project. Reads only; never transmits.

$ bussard monitor [--filter <EXPR>] [--keyring <FILE>] [--json]
Flag Default Meaning
--json off Emit JSON Lines (see JSON output) instead of the text format.
--filter <EXPR> all Only show matching telegrams: a comma-separated list of GAs, GA prefixes (3/, 3/2/) or IAs.
--keyring <FILE> the key store Keys to verify and decrypt KNX Data Secure group telegrams. The password comes from BUSSARD_KEYRING_PASSWORD.

Behaviour:

  • A group address (GA) or DPT that is not in your project degrades to raw hex, never a failure.
  • With the keys, a secured group telegram is verified and decrypted with the group key of its destination GA, decoded like a plain one and marked [secured].
  • A MAC failure shows [secured (MAC failed) seq=… raw=…], and a GA without a key shows [secured (no group key) …].
  • A sequence number that does not increase per sender adds a warning. Nothing is dropped.
  • A payload a conforming receiver ignores still decodes, with a note saying why (KNX 03_07_01 §2.4): a reserved bit set (45 on 18.001), a field out of range (hour 24 on 10.001, month 0 on 11.001, 24:30 on 19.001), tariff 255 on 5.006, or a reserved enumeration code (05 on 20.102). This is the answer to "the bus says X but nothing happened".
Details

A secured group telegram is A_SecureData with the tool-access bit clear.

bussard capture --to <DB>

Capture telegrams to a SQLite database. The schema is on JSON output.

$ bussard capture --to <DB> [--filter <EXPR>] [--keyring <FILE>]
Flag Default Meaning
--to <DB> required The database file to write; created if absent.
--filter <EXPR> all Only capture matching telegrams.
--keyring <FILE> the key store As for monitor: secured group telegrams are decrypted into the decoded snapshot, which carries the secured fields. The raw cEMI frame keeps the secured bytes.

bussard read <GA>

Send a GroupValueRead for one group address and print the typed response.

$ bussard read 3/2/0
Flag / arg Default Meaning
<GA> The group address to read, e.g. 3/2/0.
--keyring <FILE> the key store Group keys for secured GAs. The password comes from BUSSARD_KEYRING_PASSWORD.
--json off Print (schema 2, the object knx_read_group returns) {"schema", "ok", "ga", "name", "answered", "value", "typed", "dpt", "raw", "source", "secured", "admission"}. Without an answer ok and answered are false, with timeout_seconds and reason; one refused for sender admission has refused: true, sent: false, admission: "refused", reason and hint.

Behaviour:

  • Exits non-zero when nothing answers within 3 seconds, in text and JSON mode.
  • A GA with a group key, or with secure = true in groups.toml, is read with a secured GroupValueRead. Only a response whose MAC verifies under the group key is accepted, and stderr says secured: ….
  • A secured GA without a key is refused before anything is sent.
  • Before a secured read, bussard checks that the responder admits its tunnel address (see sender admission).
  • A secured read that times out says that a timeout usually means the responder does not admit the sender.

Sender admission on a secured GA

A KNX Data Secure device accepts a secured telegram only from an address in its security individual address table, the list of senders it trusts. read and write check that list before sending from the tunnel address the gateway assigned.

Evidence for each device your project links to the GA Verdict
The device's recorded table (secure_senders in bussard.lock, from bussard adopt or a verified secured apply, apply --line, flash or knx_apply_device) Admits exactly the addresses it lists.
No recorded table, but an ETS assignment of the GA to that tunnelling address in the keyring or key store Admitted.
Neither Unknown: bussard reads the device's table (PID 54) with its tool key from --keyring before sending, records it in bussard.lock and judges with it.

The read in the last row happens once per device: after it, the lock holds the table. A device without a tool key, or one that does not answer the read, stays unknown, and the note says why.

When every linked device has a table that lacks the tunnel address, the command is refused before sending:

1.1.5 does not list the tunnel address 1.1.25 as a secure sender of 1/0/4; the actuator would discard the telegram. Admit the tunnel addresses (see below) or send plain only if the GA is not secured on the device.

The refusal is followed by how to admit them. With no evidence either way, the telegram is sent and stderr says:

note: sent secured from 1.1.25; delivery to 1.1.5 is not confirmed by KNX; if nothing happens, 1.1.5 probably does not admit 1.1.25; if nothing happens, `bussard secure diag 1.1.5` ...

bussard secure diag reads the device's security failures log, which tells the causes of a dropped telegram apart (see KNX Secure).

To admit the tunnel addresses, set admit_tunnel_senders = true under [connection] and apply the device. The other ways are on KNX Secure.

bussard write <GA> <VALUE>

Write one group value to the bus, encoded against the GA's DPT from groups.toml. Nothing is stored on a device, but actuators move.

Warning

write transmits on the bus. Check the gateway the prompt names.

$ bussard write 3/0/4 on

The value is human-typed: on/off, up/down, a number, or a percentage like 75%. A 1.xxx value also takes the word pair of its sub-type (KNX 03_07_02 §3.1, and 1.100): occupied on 1.018, night on 1.024, heating on 1.100, closed/open on 1.019 (0 = closed) and open/close on 1.009 (0 = open); read and monitor print the same words. A forced-operation value (2.001-2.012, KNX 03_07_02 §3.2) is control plus the word of the matching 1.xxx sub-type, control on or control down on 2.008, or release to drop the control bit; read and monitor show Control: On or No control. A relative dimming or blind step (3.007, 3.008) is a direction and a step size: increase 25%, down 50%, up, break. The step code divides the full range into 2^(code-1) intervals (KNX 03_07_02 §3.3), so the step sizes are 100, 50, 25, 12.5, 6.25, 3.125 and 1.5625 %; increase 3 names the code directly, and a direction alone is 100 %. read and monitor print the step size: 0B on a 3.007 address is Increase 25 %. A scene number (17.001, 18.001, and scenes A/B of 1.022) counts from 1, as ETS and Home Assistant show it (KNX 03_07_02 Datapoint Types §3.19 NOTE 9, §3.1 footnote 2): scene 3 sends the field 2, so ETS scene 3 is scene 3 here. raw 2 sends the field itself. read and monitor show both: activate scene 3 (raw 2). Text, time and date have their own forms: "Hello" on a 16.000 address (ASCII, up to 14 characters, padded with 00; 16.001 takes Latin-1) and any UTF-8 text on 28.001; 12:30 or Mon 07:30:00 on 10.001; 2026-10-29 on 11.001 (1990-2089, KNX 03_07_02 §3.12); 2026-10-29 12:30:00 on 19.001, with an optional weekday and the flags summer, fault, working-day, bank-day, sync and reliable. A 19.001 value without a weekday sends the date's own one. A colour is #FF8000 or rgb(255, 128, 0) on 232.600, and #FF800010, #FF8000 or rgbw(255, 128, 0, -) on 251.600, where a channel left out (or -) is sent marked invalid (KNX 03_07_02 §6.18). read and monitor decode 242.600 to x, y and brightness, and 249.600, 250.600, 252.600 and 254.600 to their named fields. An enumeration (20.xxx, KNX 03_07_02 §3.21, §4.3, §6.3) takes its label or code: cool or 3 on 20.105; read and monitor print the label, and Unknown(18) for a reserved code. A bit set (21.xxx, 22.xxx) reads as the names of its set bits, 0A on 21.001 is Fault, InAlarm, and takes the same list or none. A 6.020 status shows its five status fields (0 = set, §3.7) and the active mode. A scaled sub-type takes the scaled value, never the raw count: 50 % on an 8.010 address sends 13 88, 1.5 s (or 1500 ms) on 7.004 sends 00 0F, 1.5 m3/h on 13.002 sends 00 00 3A 98 (KNX 03_07_02 §3.8.2, §3.9.1, §3.9.2, §3.14.1). A value outside the range or finer than the resolution is refused; read and monitor show these values with their unit. Every integer and float sub-type with a unit in KNX 03_07_02 §3.5-§3.15 shows it and takes it as a suffix: 6500 K on 7.600, 3600 s on 13.100 or 7.005, 2 K on 9.002, 50 % on 5.004; ASCII spellings work too (1 m3/h). A 5.003 angle keeps one decimal, so 80 reads 180.7 ° and 22.5 is a valid input.

Flag / arg Default Meaning
<GA> The group address to write, e.g. 3/0/4.
<VALUE> The value to encode.
--dpt <DPT> the GA's DPT The DPT to encode as.
--force off Override the protected-group-address refusal: write to a GA marked protected = true in groups.toml.
--yes off Skip the confirmation prompt. Without a terminal the command is refused unless this is given.
--json off Print (schema 2, the object knx_write_group returns) {"schema", "ok", "ga", "name", "value", "dpt", "payload", "secured", "gateway", "sent", "confirmed", "result", "admission", "note"} after the write. result is what KNX confirmed; admission is admitted, unknown or null (a plain GA); note is the unknown-delivery note. A write refused for sender admission prints ok: false, refused: true, sent: false, admission: "refused", reason and hint.
--keyring <FILE> the key store Group keys for secured GAs.

Behaviour:

  • A non-loopback gateway needs --allow-remote-gateway; the gate is checked before the prompt.
  • On a terminal it confirms, naming the GA, the decoded value and the resolved gateway. Without a terminal it refuses unless --yes is given.
  • A GA marked protected = true is refused without --force.
  • A GA with a group key, or secure = true in groups.toml, is written as a secured group telegram. A secured GA without a key is refused before anything is sent.
  • A plain GA is sent byte for byte as without keys.
  • A secured write is refused, or carries a note, as described under sender admission.
  • The result line on stderr says only what KNX confirms: the interface acknowledged the telegram (L_Data.con); KNX reports no application-level result. A group write gets no reply from the device. When the confirmation is not seen in time the line says so, and the exit code stays 0.
Details

A secured group telegram uses SCF 0x10, the group key and a sequence number above the last one sent. The receiver's list of trusted senders is the security individual address table (PID 54).

bussard learn

Name and type group addresses from live traffic. learn prompts you to trigger an object, waits for the telegram, and proposes a name and DPT.

$ bussard learn [--ga <GA>]... [--unnamed] [--untyped] [--timeout <SECS>] [--yes]

For each telegram it shows the sender, its channel and com object, the payload, ranked DPT candidates with a reason for each, and a name built from the device's room, channel and com-object function. You accept, edit the name, change the DPT, skip, or quit.

Flag Default Meaning
--ga <GA> Learn this group address. Repeatable; learned in the order given.
--unnamed off Learn every GA in your project whose name is a placeholder (empty, the address itself, GA <address>, Unnamed, Unknown...).
--untyped off Learn every GA in your project with no DPT (the ones validate reports as W011).
--yes off Skip the confirmation prompt: accept the top candidate and the proposed name. Without a terminal the command is refused unless this is given.
--timeout <SECS> 30 How long to wait for each telegram.
--keyring <FILE> the key store ETS .knxkeys keyring whose group keys decrypt secured group telegrams. The password comes from BUSSARD_KEYRING_PASSWORD.

Behaviour:

  • learn never transmits. It listens on the same connection monitor uses.
  • With neither --ga nor --unnamed/--untyped, it takes whatever appears on the bus next, one GA at a time, until a wait times out or you quit.
  • Accepted answers go into groups.toml. When the sending com object can be pinned down (an existing link, or exactly one free transmit-capable object on the sending device), the sending device's file gets the send link too.
  • A DPT candidate is ranked high only when the sending com object declares that DPT in your project. Payload shape alone gives medium at most, because most payload lengths fit several DPTs. Repeated telegrams on one GA narrow the candidates.
  • With the keys, a secured telegram is verified and decrypted as in monitor --keyring, and the inference runs on the decrypted value. The stdout line ends in , secured), and the learned group gets secure = true in groups.toml, so read, write, flash and apply treat it as secured.
  • A secured telegram that cannot be verified (no keys, no group key for the GA, a MAC failure) is reported and skipped. learn never guesses a DPT from ciphertext.
  • A sequence number that does not increase over the sender's last one prints the warning monitor shows.

bussard test

Run the acceptance tests in tests.toml against the bus and print a pass/fail report. Each test writes a group value, or prints a manual instruction and waits for Enter, then waits for the expected telegram.

Warning

test writes to the bus. It goes through the same rails as bussard write.

$ bussard test [--file <FILE>] [--only <NAME>]... [--skip-manual] [--yes]
Flag Default Meaning
--file <FILE> <dir>/tests.toml The test file to run. See tests.toml.
--json off Print the report as JSON: started_at, tests[] (name, status of pass/fail/skipped/refused, detail, observed) and summary counts.
--force off Override the protected-group-address refusal: write to a GA marked protected = true in groups.toml. The test also needs allow_protected = true in the test file.
--skip-manual off Report manual: tests as skipped instead of prompting. Without a terminal they are skipped anyway.
--only <NAME> all Run only the named test (case-insensitive). Repeatable.
--yes off Skip the confirmation prompt. Without a terminal the command is refused unless this is given.
--secure-idle <SECS> Instead of running tests.toml: measure the KNXnet/IP Secure session idle timeout. See below.

Behaviour:

  • A non-loopback gateway needs --allow-remote-gateway, and the run confirms on a terminal naming the gateway.
  • The keys serve the tunnel only: tests send plain group telegrams.
  • A test that writes to a protected = true GA needs both allow_protected = true in the file and --force. With either missing it is reported as refused and nothing is sent to that GA.
  • A failing expectation reports the value that did arrive on the expected GA.
  • Exits non-zero when any test fails. Skipped and refused tests do not fail the run.
  • The text report has no timestamps, so two runs over a healthy installation are byte-identical. The JSON report adds only started_at.

Measuring the secure session timeout

bussard test --secure-idle <SECS> opens a KNXnet/IP Secure session with the interface, sends nothing for SECS seconds, then checks whether the session is still alive. It prints one line:

Result Meaning
ALIVE The interface answered.
DROPPED after <t> s (<reason>) The interface ended the session or closed the connection.
SILENT No answer.
  • The credentials come from the key store (or --keyring), or from --secure-user/--secure-password-env. Without any, it refuses and names them. The session runs over TCP only (KNX IP Secure 3/8/9 §2.2.3.3).
  • --json prints the same as an object: outcome, after_ms, reason, answered_ms, transport, user_id.
  • It uses no tunnel slot and nothing reaches the bus, so it needs neither --yes nor --allow-remote-gateway.
  • Run it with growing SECS (say 45, 65, 90, 125) to bracket the interface's timeout.
Details